Product Description
Vertiv NetSure 7100 DC power system, -48V DC Power System – 20 kW to 600 kW -582127000
The modular NetSure 7100 Series power system with 3500 watt or 2000 watt rectifiers and DC to DC converters provides up to 12,000 amps of current for -48 volt systems with up to 520 amps at +24 volts or -58 volts. The basic components of the power system include the NetSure Control Unit (NCU), module mounting shelf assemblies which house the rectifiers and converters, and a modular distribution cabinet.
Other Details
(Manufacturer Standard Warranty) - Not Clear what product you need, or can't find your specific product/service part number? Call us +1 888 988 5472 | Fax: +1 888 920 3445.Product Videos
Custom Field
Manufacturer Part Number 582127000
Power Capacity 600 kW (6 bays)
Current Capacity 12,000 A (6 bays)
System Type Cabinet or Relay Rack
Input Voltage, Nominal 208 VAC to 277/480 VAC
Input Voltage, Operational 176 VAC to 305/528 VAC
Input Connections Terminal Blocks or Line Cords
Equipment Dimensions (H x W x D) D Cabinet:12.2" (7RU) to 33.25" (19RU) x 23" x 20.1", R Shelves:1.7" (1RU) or 5.2" (3RU) x 23" x 20.1"
Access Front for installation, operation and maintenance, Rear for multi-bay, rectifier shelf or battery tray expansion
Output Voltage, Nominal -48 VDC, +24 VDC, -58 VDC
Output Voltage, Operational Rectifier: -42 VDC to -58 VDC; Converter: +24 VDC to +28 VDC or -56 VDC to -58 VDC
Output Capacity Up to 2000 amps per bay at -48 VDC plus redundancy, maximum of six bays; Up to 520 amps at +24 VDC or -58 VDC plus redundancy
Peak Efficiency Rectifier: 96.5%; Converter: 95% (+24 VDC or -58 VDC)
Load Circuit Breakers / Fuses Up to (104) Bullet CBs, 1 to 300 A, Up to (24) GJ/218 CBs, 100 to 800 A, Up to (16) TPH Fuses, 70 to 600 A, Up to (16) TBL-B Fuses, 70 to 250 A
Battery Circuit Breakers / Fuses Up to (24) Bullet CBs, 1 to 300 A, Up to (4) GJ/218 CBs, 100 to 800 A, Up to (4) TPH Fuses, 70 to 600 A /up to 200A CB Disconnect mounted on each batt
Options Low Voltage Load Disconnect, Low Voltage Batttery Disconnect, Battery Shunt, Battery Trays - Pre-cabled, Bulk Output Panel, Up to (68) Temp Sensors
Weight 90.9 to 295.5 kg
Control and Monitoring Dual Ethernet, Embedded web pages, SNMP, Modbus, Battery Management, Programmable Relay Outputs and Binary Inputs, Energy Management
Operating Temperature -40 °C to +40 °C (-40 °F to +104 °F)
Safety Compliance UL 1801 Listed (“c UL”), NEBS Level 3
EMC Compliance FCC Class B
Note Images may not be exact, please check specifications.
Required A Volume Purchase Contact us for a volume pricing | volumeorders@hssl.us